Wood calculators / Firewood & heating
Measure the wood. State the basis.
Wood Stove Heat Demand Scenario Calculator
Calculate a simplified steady-state fabric and air-change heat-loss scenario in kW and BTU/h.
Your wood & project inputs
Your result
Ready to calculateEnter your values and press Calculate. The result will open on the calculation page.
Published references · Clear assumptions · No sign-up
The method
Formula and calculation steps
Heat loss = [Σ(U×area) + air density×cp×ACH×volume/3600] × temperature difference.
Calculate a simplified steady-state fabric and air-change heat-loss scenario in kW and BTU/h.
- Confirm the physical, product or tally basis and use the stated units.
- Enter actual measurements and justified properties, prices or project allowances.
- Submit the form, then interpret the result with the assumptions and limits below.
Not a full room-by-room design load, stove recommendation, chimney assessment or installation check. Thermal bridges, infiltration details and other gains/losses are not resolved.
Wood Stove Heat Demand Scenario: formula, units and interpretation
Calculate a simplified steady-state fabric and air-change heat-loss scenario in kW and BTU/h. Not a full room-by-room design load, stove recommendation, chimney assessment or installation check. Thermal bridges, infiltration details and other gains/losses are not resolved.
Separate the measured physical quantity from the purchase or design convention. Nominal lumber names, finished dimensions, geometric board feet, log-rule yield, stacked cords and mass describe different things. The method on this page uses only the basis stated beside its inputs; do not replace a missing property with an unrelated unit or trade name.
Before using the answer for a real project, confirm measurements and the relevant supplier information. Entered waste, prices, material properties and limits remain user choices. A rounded purchasing count is a quantity allowance rather than a cutting plan, and a calculated physical response is not a building-code approval.
Continue with: Firewood Cord Calculator · Solid Wood to Cords Calculator · Firewood Cost Calculator · Firewood Useful Heat Calculator
Check the numbers
Wood Stove Heat Demand Scenario Calculator: calculated examples
These scenarios are computed with the same method as the form. They are not stock recommendations, current quotes, code design values or full standards tables.
Worked example with stated inputs
Dimension units = Metric (m / mm); Net wall area = 40 m²; Entered wall U-value = 0.5 W/m²K; Window area = 5 m²; Entered window U-value = 2 W/m²K; Roof / ceiling area = 20 m²; Entered roof U-value = 0.3 W/m²K; Room air volume = 50 m³; Entered air changes = 0.5 1/h; Assumed air density = 1.2 kg/m³; Assumed air heat capacity = 1005 J/kgK; Indoor minus outdoor temperature = 20 K.
| Output | Computed result |
|---|---|
| Steady-state room heat-loss scenario | 0.8875 kW |
| Heat loss | 3,028.275699 BTU/h |
| Fabric conductance | 36 W/K |
| Air-change conductance | 8.375 W/K |
How the stated input changes the result
| Scenario | Changed input / basis | Result |
|---|---|---|
| 10 K | Indoor minus outdoor temperature | 0.44375 kW |
| 15 K | Indoor minus outdoor temperature | 0.665625 kW |
| 20 K | Indoor minus outdoor temperature | 0.8875 kW |
| 25 K | Indoor minus outdoor temperature | 1.109375 kW |
| 30 K | Indoor minus outdoor temperature | 1.33125 kW |
| 40 K | Indoor minus outdoor temperature | 1.775 kW |
Unchanged inputs use: Dimension units = Metric (m / mm); Net wall area = 40 m²; Entered wall U-value = 0.5 W/m²K; Window area = 5 m²; Entered window U-value = 2 W/m²K; Roof / ceiling area = 20 m²; Entered roof U-value = 0.3 W/m²K; Room air volume = 50 m³; Entered air changes = 0.5 1/h; Assumed air density = 1.2 kg/m³; Assumed air heat capacity = 1005 J/kgK; Indoor minus outdoor temperature = 20 K. Results retain the model limitations described above.
Common questions
Is there a universal kW per room volume?
No. Envelope performance, outside conditions, ventilation and other factors change the demand.
Can I use this as a wood burner size recommendation?
No. It calculates only the stated simplified heat-loss model; product selection and installation need the proper assessment.
Where do U-values come from?
Supply appropriate assembly data in W/m²K. The example values are arithmetic inputs, not code requirements.
How do I use this wood stove heat demand scenario calculator?
Calculate a simplified steady-state fabric and air-change heat-loss scenario in kW and BTU/h. Heat loss = [Σ(U×area) + air density×cp×ACH×volume/3600] × temperature difference. Read the dimensioned examples below before entering project values.
Do starting values represent product or code recommendations?
No. They are stated calculation examples. Verify actual dimensions, material or product properties, units and site conditions. Neither a positive result nor an example value establishes a certified product, allowed load, compliant layout or current market price.
Can I export the result to Excel?
After calculating, use Export CSV. Excel can open the numeric results and submitted inputs. This is a text export, not a native formula workbook, desktop app or downloadable design package.
Where do the formulas and data come from?
Method and material references are listed below as plain-text addresses. Dimensional tables are calculated here from the stated inputs. Product density examples retain their species, moisture or manufacturer basis. Sources are not fetched when you use the calculator.
Related calculators
Formula sources and references
References support the underlying methods and units. Chosen example inputs are not universal recommendations, supplier ratings, market prices or code limits.
- US DOE / PNNL Building America: heat flow, U-factor, area and temperature differencehttps://basc.pnnl.gov/information/building-science-introduction-heat-flow
- US DOE Fundamentals Handbook Volume 2: heat capacity and energy balancehttps://archives.standards.doxcelerate.com/documents/doe-hdbk-1012-2-92-thermodynamics-heat-transfer-and-fluid-flow-volume-2-of-3
- US Department of Energy: Home Heating, efficiency and proper sizing; wood/pellet-stove installation instructionshttps://www.energy.gov/sites/default/files/2014/01/f6/homeHeating.pdf
- NIST SP 811, Appendix B.9: mass, length, area and volume conversion factorshttps://www.nist.gov/pml/special-publication-811/nist-guide-si-appendix-b-conversion-factors/nist-guide-si-appendix-b9